File Download

There are no files associated with this item.

  Links for fulltext
     (May Require Subscription)
Supplementary

Article: Potential airborne transmission between two isolation cubicles through a shared anteroom

TitlePotential airborne transmission between two isolation cubicles through a shared anteroom
Authors
KeywordsFull-scale field experiment
Computational fluid dynamic (CFD) simulation
Door motion
Inter-cubicle airborne transmission
Isolation room
Issue Date2015
Citation
Building and Environment, 2015, v. 89, p. 264-278 How to Cite?
Abstract© 2015 Elsevier Ltd. Full-scale experiments and CFD simulations were performed to study potential inter-cubicle airborne transmissions through a shared anteroom due to the hinged door opening. When doors are closed, current negative pressure designs are effective for the containment of airborne pathogens in the 'dirty' cubicle with an index patient. When the 'dirty' cubicle door is open, airborne agents can move into the other 'clean' cubicle via the shared anteroom. As the door being opened or closed, the door sweeping effect is the main source of the two-way airflow and contaminant exchange through the doorway. When the dirty cubicle door remains fully open, temperature difference and concentration gradient across the doorway induce the two-way buoyancy-driven flow and transport of airborne agents across the doorway. The longer the dirty cubicle door remains fully open (10s, 30s or 60s) or the smaller the air change rate (34-8.5 ACH for each cubicle), the more airborne pathogens are being transported into the 'clean' cubicle and the longer time it takes to remove them after the door is closed. Keeping the door completely open is potentially responsible for the majority of inter-cubicle transmissions if its duration is much longer than the duration of door motion (only 3s). Our analyses suggest a potential inter-cubicle infection risk if the shared anteroom is used for multiple isolation cubicles. Decreasing the duration of door opening, raising air change rate or using a curtain at the doorway are recommended to reduce inter-cubicle exposure hazards.
Persistent Identifierhttp://hdl.handle.net/10722/260188
ISSN
2021 Impact Factor: 7.093
2020 SCImago Journal Rankings: 1.736
ISI Accession Number ID

 

DC FieldValueLanguage
dc.contributor.authorHang, Jian-
dc.contributor.authorLi, Yuguo-
dc.contributor.authorChing, W. H.-
dc.contributor.authorWei, Jianjian-
dc.contributor.authorJin, Ruiqiu-
dc.contributor.authorLiu, Li-
dc.contributor.authorXie, Xiaojian-
dc.date.accessioned2018-09-12T02:00:40Z-
dc.date.available2018-09-12T02:00:40Z-
dc.date.issued2015-
dc.identifier.citationBuilding and Environment, 2015, v. 89, p. 264-278-
dc.identifier.issn0360-1323-
dc.identifier.urihttp://hdl.handle.net/10722/260188-
dc.description.abstract© 2015 Elsevier Ltd. Full-scale experiments and CFD simulations were performed to study potential inter-cubicle airborne transmissions through a shared anteroom due to the hinged door opening. When doors are closed, current negative pressure designs are effective for the containment of airborne pathogens in the 'dirty' cubicle with an index patient. When the 'dirty' cubicle door is open, airborne agents can move into the other 'clean' cubicle via the shared anteroom. As the door being opened or closed, the door sweeping effect is the main source of the two-way airflow and contaminant exchange through the doorway. When the dirty cubicle door remains fully open, temperature difference and concentration gradient across the doorway induce the two-way buoyancy-driven flow and transport of airborne agents across the doorway. The longer the dirty cubicle door remains fully open (10s, 30s or 60s) or the smaller the air change rate (34-8.5 ACH for each cubicle), the more airborne pathogens are being transported into the 'clean' cubicle and the longer time it takes to remove them after the door is closed. Keeping the door completely open is potentially responsible for the majority of inter-cubicle transmissions if its duration is much longer than the duration of door motion (only 3s). Our analyses suggest a potential inter-cubicle infection risk if the shared anteroom is used for multiple isolation cubicles. Decreasing the duration of door opening, raising air change rate or using a curtain at the doorway are recommended to reduce inter-cubicle exposure hazards.-
dc.languageeng-
dc.relation.ispartofBuilding and Environment-
dc.subjectFull-scale field experiment-
dc.subjectComputational fluid dynamic (CFD) simulation-
dc.subjectDoor motion-
dc.subjectInter-cubicle airborne transmission-
dc.subjectIsolation room-
dc.titlePotential airborne transmission between two isolation cubicles through a shared anteroom-
dc.typeArticle-
dc.description.naturelink_to_subscribed_fulltext-
dc.identifier.doi10.1016/j.buildenv.2015.03.004-
dc.identifier.scopuseid_2-s2.0-84925615003-
dc.identifier.hkuros254594-
dc.identifier.volume89-
dc.identifier.spage264-
dc.identifier.epage278-
dc.identifier.isiWOS:000364440600023-
dc.identifier.issnl0360-1323-

Export via OAI-PMH Interface in XML Formats


OR


Export to Other Non-XML Formats