Conference Paper: Application potential of ground-coupled heat pumps for multi-storey office buildings in Hong Kong

TitleApplication potential of ground-coupled heat pumps for multi-storey office buildings in Hong Kong
Authors
KeywordsChiller system
Coefficients of performance
Cooling load
Ground thermal conductivity
Ground-coupled heat pump
Hong-kong
Land areas
Undisturbed ground temperature
Issue Date2011
Citation
The 12th Conference of International Building Performance Simulation Association (BS 2011), Sydney, NSW., Australia, 14-16 November 2011. In Proceedings of Building Simulation 2011, 2011, p. 64-69 How to Cite?
AbstractIn this paper, the application potential of ground-coupled heat pumps (GCHP) in a multi-storey office building in Hong Kong was investigated. It was found that within the limited land area occupied by the building, the GCHP could only handle the cooling load for one floor over a range of the ground thermal conductivities and undisturbed ground temperatures. The year-round energy consumption of the GCHP was compared with those using the conventional vapour-compression chiller systems. An energy saving of at least 13.2% and 2.6% could be achieved against those using an air-cooled and a water-cooled vapour-compression chiller with rated coefficients of performance equal to 3.0 and 5.0 respectively.
Persistent Identifierhttp://hdl.handle.net/10722/166908

 

DC FieldValueLanguage
dc.contributor.authorLee, CKen_US
dc.contributor.authorLam, HNen_US
dc.date.accessioned2012-09-21T01:43:33Z-
dc.date.available2012-09-21T01:43:33Z-
dc.date.issued2011en_US
dc.identifier.citationThe 12th Conference of International Building Performance Simulation Association (BS 2011), Sydney, NSW., Australia, 14-16 November 2011. In Proceedings of Building Simulation 2011, 2011, p. 64-69en_US
dc.identifier.urihttp://hdl.handle.net/10722/166908-
dc.description.abstractIn this paper, the application potential of ground-coupled heat pumps (GCHP) in a multi-storey office building in Hong Kong was investigated. It was found that within the limited land area occupied by the building, the GCHP could only handle the cooling load for one floor over a range of the ground thermal conductivities and undisturbed ground temperatures. The year-round energy consumption of the GCHP was compared with those using the conventional vapour-compression chiller systems. An energy saving of at least 13.2% and 2.6% could be achieved against those using an air-cooled and a water-cooled vapour-compression chiller with rated coefficients of performance equal to 3.0 and 5.0 respectively.-
dc.languageengen_US
dc.relation.ispartofProceedings of Building Simulation 2011en_US
dc.subjectChiller system-
dc.subjectCoefficients of performance-
dc.subjectCooling load-
dc.subjectGround thermal conductivity-
dc.subjectGround-coupled heat pump-
dc.subjectHong-kong-
dc.subjectLand areas-
dc.subjectUndisturbed ground temperature-
dc.titleApplication potential of ground-coupled heat pumps for multi-storey office buildings in Hong Kongen_US
dc.typeConference_Paperen_US
dc.identifier.emailLam, HN: hremlhn@hkucc.hku.hken_US
dc.identifier.authorityLam, HN=rp00132en_US
dc.description.naturepublished_or_final_version-
dc.identifier.scopuseid_2-s2.0-84870204123-
dc.identifier.hkuros195922en_US
dc.identifier.hkuros210211-
dc.identifier.spage64en_US
dc.identifier.epage69en_US