Article: Limit cycles in power systems due to OLTC deadbands and load-voltage dynamics
Title | Limit cycles in power systems due to OLTC deadbands and load-voltage dynamics |
---|---|
Authors | |
Keywords | Limit Cycles Load-Voltage Dynamics Oltc Deadbands |
Issue Date | 1998 |
Publisher | Elsevier SA. The Journal's web site is located at http://www.elsevier.com/locate/epsr |
Citation | Electric Power Systems Research, 1998, v. 47 n. 3, p. 181-188 How to Cite? |
Abstract | In this paper, the phenomenon of limit cycle due to load-tap changer interaction is investigated. The role of OLTC deadband in creating a limit cycle phenomenon is addressed. The impact of tap dynamics modelling on system/voltage behaviour is carefully considered. Analytical insights into observed behaviour of power systems with different tap models are given using eigenvalue analysis, the describing function method and time simulation. The conditions for occurrence of limit cycles and the identification of key parameters influencing their characteristics are another important aspect of this investigation. © 1998 Elsevier Science S.A. All rights reserved. |
Persistent Identifier | http://hdl.handle.net/10722/169664 |
ISSN | 2023 Impact Factor: 3.3 2023 SCImago Journal Rankings: 1.029 |
References |
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Larsson, M | en_US |
dc.contributor.author | Popović, DH | en_US |
dc.contributor.author | Hill, DJ | en_US |
dc.date.accessioned | 2012-10-25T04:54:04Z | - |
dc.date.available | 2012-10-25T04:54:04Z | - |
dc.date.issued | 1998 | en_US |
dc.identifier.citation | Electric Power Systems Research, 1998, v. 47 n. 3, p. 181-188 | en_US |
dc.identifier.issn | 0378-7796 | en_US |
dc.identifier.uri | http://hdl.handle.net/10722/169664 | - |
dc.description.abstract | In this paper, the phenomenon of limit cycle due to load-tap changer interaction is investigated. The role of OLTC deadband in creating a limit cycle phenomenon is addressed. The impact of tap dynamics modelling on system/voltage behaviour is carefully considered. Analytical insights into observed behaviour of power systems with different tap models are given using eigenvalue analysis, the describing function method and time simulation. The conditions for occurrence of limit cycles and the identification of key parameters influencing their characteristics are another important aspect of this investigation. © 1998 Elsevier Science S.A. All rights reserved. | en_US |
dc.language | eng | en_US |
dc.publisher | Elsevier SA. The Journal's web site is located at http://www.elsevier.com/locate/epsr | en_US |
dc.relation.ispartof | Electric Power Systems Research | en_US |
dc.subject | Limit Cycles | en_US |
dc.subject | Load-Voltage Dynamics | en_US |
dc.subject | Oltc Deadbands | en_US |
dc.title | Limit cycles in power systems due to OLTC deadbands and load-voltage dynamics | en_US |
dc.type | Article | en_US |
dc.identifier.email | Hill, DJ: | en_US |
dc.identifier.authority | Hill, DJ=rp01669 | en_US |
dc.description.nature | link_to_subscribed_fulltext | en_US |
dc.identifier.scopus | eid_2-s2.0-0032209193 | en_US |
dc.relation.references | http://www.scopus.com/mlt/select.url?eid=2-s2.0-0032209193&selection=ref&src=s&origin=recordpage | en_US |
dc.identifier.volume | 47 | en_US |
dc.identifier.issue | 3 | en_US |
dc.identifier.spage | 181 | en_US |
dc.identifier.epage | 188 | en_US |
dc.publisher.place | Switzerland | en_US |
dc.identifier.scopusauthorid | Larsson, M=15819476500 | en_US |
dc.identifier.scopusauthorid | Popović, DH=22956344500 | en_US |
dc.identifier.scopusauthorid | Hill, DJ=35398599500 | en_US |
dc.identifier.issnl | 0378-7796 | - |